Expected vs observed
What the campus should be doing at its age, load and weather — from manufacturer and engineering sources — against what the satellites see. Residuals are diagnostic targets with ranked physical hypotheses, never causal findings.
Cooling-configuration prior
Peer comparison — finished roofs
≥8 confirming clean acquisitions, ≥60 days, ≥2 platforms, deviation ≥0.03 below the completed-membrane peer median
Same-acquisition deviation from the completed-membrane peer median removes sun geometry, atmosphere and reference drift. Landsat thermal deviation from the other roofs is an independent series with mixed 100 m pixels.
Same-day matches (≤1 day) across landsat-8, landsat-9, sentinel-2a, sentinel-2b, sentinel-2c; both quantities peer-normalized at the same acquisition. The relationship holds in low and high irradiance and both seasons (low ghi r -0.48, n 205; high ghi r -0.51, n 215; cool season r -0.53, n 343; warm season r -0.32, n 77). Roofs that read darker than their peers run hotter. Every roof is a mixed 100 m thermal pixel — agreement across sensors is necessary for a physical reading, not attribution of cause.
ObservedGeneral Roof 8 · DATA_HALL_01 — clean-control candidate, not a verified control
visually clean-control candidate (no analyst soiling tag) whose spectral state is below its expected age-adjusted baseline (now/plateau 0.846 vs 0.920); not a verified control. Its Landsat peer temperature is slightly below peers, so the two sensors disagree on this roof. It stays the observation target for a wash test rather than the baseline the experiment is measured against.
The three configuration priors the engine carries for this campus, each evaluated hourly on the same weather, load prior and prices. Water-cooled plants trade electricity for water; dry heat rejection trades water for electricity — no single metric is optimized in isolation. Weights are the evidence-weighted prior, not a finding.
Prior
Weight
Annual PUE
Overhead MWh/yr
Peak overhead kW
Overhead cost/yr
Economizer hours
Water m³/yr
B ac chiller dry
0.45
1.241
355,016
59,685
$13.0M
11 %
0
A wc chiller tower
0.3
1.209
308,235
44,690
$11.4M
28 %
3,128,614
C liquid it external
0.25
1.121
178,797
22,335
$6.7M
28 %
2,902,123
Evidence-weighted PUE 1.202 on an assumed IT load. An equipment schedule collapses this table to one row.
Engine residuals
Modeled
Residuals from engine run 78a2537c on graph B_ac_chiller_dry. Roof residuals compare the last-60-day observed reflectance ratio (vs each roof's own plateau) with the age-adjusted expectation; thermal residuals are peer-normalized Landsat ST. Residuals are diagnostic targets, not causal findings.
Baseline degradation curve — white TPO reflectance vs age
What a white TPO roof should reflect as it ages (manufacturer CRRC initial and 3-year aged anchors, interpolated; the band is the manufacturer spread, never averaged), with each roof's satellite-measured reflectance at its actual age. Dots below the band are roofs reflecting less sunlight than their age explains.
8 of 8 roofs measure below the manufacturer's expected range for their age.
Expected for a clean-aged roof (manufacturer)
Manufacturer range
Measured roof (satellite)
Clean control roof
Correlated system graph
Modeled
How a change anywhere on the campus moves through cooling, power and compute. Every line carries its physics: function, units, uncertainty and source.
How to read this: left to right is the order energy moves. Weather and sun heat the roofs and the IT equipment makes heat; the cooling plant removes it, rejects it outdoors and draws electricity; that electricity shows up in facility power, PUE and the compute capacity left over. Pick an intervention to light up every part of the system it changes.
Trace an intervention:
Weather input
Physical asset
Plant or system
Result we report
Dashed: waiting on owner data
Wear or soiling flagged
Traced intervention
Thicker lines carry more assets. Click any box or line for detail.
Which assets and interactions have the most leverage under this cooling prior, from the engine's design-day sweeps. Every label is prefixed MODELED because no plant observation exists.
High leverage asset · rank 15,230 kW overhead (design day)
MODELED: dry-cooler coil_fouled
High leverage asset · rank 22,486 kW overhead (design day)
MODELED: CRAH filter_loaded
High leverage asset · rank 382 kW overhead (design day)
MODELED: roof insulation_wet_partial (all roofs)
High leverage asset · rank 441 kW overhead (design day)
MODELED: roof soiled_heavy (all roofs)
High leverage asset · rank 516 kW overhead (design day)
MODELED: roof soiled_moderate (all roofs)
High leverage asset · rank 60 kW overhead (design day)
MODELED: chiller condenser_fouled
High leverage asset · rank 70 kW overhead (design day)
MODELED: tower fill_scaled
High leverage asset · rank 80 kW overhead (design day)
On a campus under construction a step-up is usually membrane completion; the Timeline page checks each step against the land-state classifier's completion date and says which it is.
Peer normalized surface temp c
-0.74
128/183 · 700 d
lower reflectance than expected (soiling / weathering)
lower reflectance than expected (soiling / weathering)
Facility-level expected state — observed mechanical performance pending
The engine evaluates the whole system hourly on real weather. The observed column stays owner-data-required until BAS trends or 15-minute facility power arrive; that dataset turns every mechanical counterfactual from a modeled scenario on an inferred state into an observed residual with a measured uplift. See the observed-mechanical-performance surface.
Metric
Expected (30-day mean)
Observed
Residual
Facility power
IT load
PUE
Chiller power
Auxiliaries (pumps, fans)
Roof heat gain (all roofs)
Cooling demand
Available compute power
Versico VersiWeld TPO · piecewise_linear · manufacturer stated. Anchors: CRRC initial and 3-year uncleaned (manufacturer). Year-1 front-loading and >3-year tail are inferred (LBNL soiling literature); high band carries the Firestone 0.83 conflict. Measured values are each roof's same-day cohort albedo; age is from its recorded install date. Hover a dot for its numbers.
Roof priors in the active knowledge version
Initial solar reflectance3-year aged (uncleaned)Cleaning recovery fractionSoiling rate, first yearDesign R prior 1Design R prior 2Design R prior 3Design R prior 4Design R prior 5Design R prior 6
Version dc-baseline v1.2.0 · 203 metrics · 56 curves · membrane is a visually inferred candidate, not a verified product.
MODELED: economizer plates_fouled
High leverage asset · rank 90 kW overhead (design day)